MTL 5511 SWITCH/PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2, (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater power supply 4/20mA, HART®, 2- or 3-wire transmitters
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signal) - 51mA at 24V
  • Power dissipation within unit (with 20mA signal): MTLx541 0.7W @ 24V dc.
  • MTLx541S 1.0W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5561 FIRE AND SMOKE DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (, 0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Fire and Smoke Detector Interface
  • Number of channels: Two, fully floating, loop powered.
  • Input voltage: 6 to 30V dc
  • Current range: 1 to 40mA, nominal
  • Maximum output voltage: 28V from 300Ohms
  • Power dissipation within unit:
  • 0.7W maximum at 24V with 40mA signal (each channel)
  • 0.9W maximum at 30V with 40mA signal (each channel)

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5516C SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: 2, with line fault detection
  • Hazardous-area inputs: Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 35mA at 24V
  • Power dissipation within unit: 0.84W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5525 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Solenoid/Alarm Driver, switch operated with override, IIC, low power
  • Number of channels: One
  • Hazardous-area output:
  • Minimum output voltage: 7V at 48mA
  • Maximum output voltage: 24V from 300Ohms
  • Current limit: 48mA
  • Maximum current consumption: 100mA at 24V dc
  • Power dissipation within unit:
  • 1.3W with typical solenoid valve, output on
  • 1.9W worst case

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5544 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater Power Supply, 4/20mA, HART®, 2- or 3- wire transmitters
  • Number of channels: Two
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit (with 20mA signals): MTLx544 1.4W @ 24V dc
  • MTLx544S 1.9W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5541 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I



ATEX, IECEx
  • Switch/ ProximityDetector Interface
  • Number of channels: One
  • Hazardous-area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5514 SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: One
  • Hazardous–area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V dc
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5521 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I

ATEX, IECEx
  • Solenoid/ Alarm Driver, loop-powered, IIC
  • Number of channels: One
  • Hazardous-area output: (MTLx521)
  • Minimum output voltage: 12.8V at 48mA
  • Maximum output voltage: 24V from 180Ohms
  • Current limit: 48mA
  • Maximum current consumption: 90mA at 24V
  • Power dissipation within unit:1.4W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 5544D REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I
ATEX, IECEx
  • Repeater Power Supply
  • single channel, 4/20mA, HART®, 2- or 3-wire transmitters, two outputs
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mAUnder/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption: (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit: (with 20mA signals) 1.4W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4511 SWITCH/PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater power supply 4/20mA, HART®, 2- or 3-wire transmitters
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signal) - 51mA at 24V
  • Power dissipation within unit (with 20mA signal): MTLx541 0.7W @ 24V dc.
  • MTLx541S 1.0W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4561 FIRE AND SMOKE DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Fire and Smoke Detector Interface
  • Number of channels: Two, fully floating, loop powered.
  • Input voltage: 6 to 30V dc
  • Current range: 1 to 40mA, nominal
  • Maximum output voltage: 28V from 300Ohms
  • Power dissipation within unit:
  • 0.7W maximum at 24V with 40mA signal (each channel)
  • 0.9W maximum at 30V with 40mA signal (each channel)

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4516C SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: 2, with line fault detection
  • Hazardous-area inputs: Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 35mA at 24V
  • Power dissipation within unit: 0.84W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4525 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Solenoid/Alarm Driver, switch operated with override, IIC, low power
  • Number of channels: One
  • Hazardous-area output:
  • Minimum output voltage: 7V at 48mA
  • Maximum output voltage: 24V from 300Ohms
  • Current limit: 48mA
  • Maximum current consumption: 100mA at 24V dc
  • Power dissipation within unit:
  • 1.3W with typical solenoid valve, output on
  • 1.9W worst case

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4544 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Repeater Power Supply, 4/20mA, HART®, 2- or 3- wire transmitters
  • Number of channels: Two
  • Safe-area output: Signal range: 4 to 20mA. Under/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit (with 20mA signals): MTLx544 1.4W @ 24V dc
  • MTLx544S 1.9W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4541 REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I

ATEX, IECEx
  • Switch/ ProximityDetector Interface
  • Number of channels: One
  • Hazardous-area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4514 SWITCH/ PROXIMITY DETECTOR INTERFACE
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA nC IIC T4 Gc

Ex II (1) GD
[Ex ia] IIC
[Ex iaD]
Ex I (M1) [Ex ia] I
ATEX, IECEx
  • Switch/ Proximity Detector Interface
  • Number of channels: One
  • Hazardous–area inputs
  • Inputs conforming to BS EN60947–5–6:2001 standards for
  • proximity detectors (NAMUR)
  • Voltage applied to sensor: 7 to 9V dc from 1kOhms ±10%
  • Maximum current consumption: 25mA at 24V dc
  • Power dissipation within unit: 0.6W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4521 SOLENOID/ALARM DRIVER
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I
ATEX
  • Solenoid/ Alarm Driver, loop-powered, IIC
  • Number of channels: One
  • Hazardous-area output: (MTLx521)
  • Minimum output voltage: 12.8V at 48mA
  • Maximum output voltage: 24V from 180Ohms
  • Current limit: 48mA
  • Maximum current consumption: 90mA at 24V
  • Power dissipation within unit:1.4W at 24V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 4544D REPEATER POWER SUPPLY
INTRINSICALLY SAFE ISOLATOR
Zones: 2 (0, 1, 2, 20, 21, 22)
Ex II 3 G
Ex nA IIC T4

Ex II (1) GD
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex I (M1) [Ex ia Ma] I
ATEX, IECEx
  • Repeater Power Supply
  • single channel, 4/20mA, HART®, 2- or 3-wire transmitters, two outputs
  • Number of channels: One
  • Safe-area output: Signal range: 4 to 20mAUnder/over-range: 0 to 24mA
  • Hazardous-area input: Signal range: 0 to 24mA (including over-range)
  • Transmitter voltage: 16.5V at 20mA
  • Maximum current consumption: (with 20mA signals) 96mA at 24V dc
  • Power dissipation within unit: (with 20mA signals) 1.4W @ 24V dc

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7706+ 'SMART' 2-WIRE 4/20MA TRANSMITTER
ZENER BARRIER
Zones: 2
Ex II 3 G
Ex nA IIC T4 Gc

II (1) GD [Ex ia Ga] IIC
(-20°C to +60°C)

II (1) GD [Ex ia Da] IIIC
(-20°C to +60°C)

ATEX, IECEx
  • Number of channels: one
  • Safe-area output: Signal range: 4 to 20mA
  • Pass Incoming Communications Signals up to: 10kHZ
  • Supply Voltage: 20 to 35V dc w.r.t earth
  • Output Current: 4 to 20 mA
  • Safe-area Load Resistance: 0 to 500 Ohms
  • Supply Current: 45mA (typical at 20mA and 24V supply)
  • Supply Current: 60mA (maximum at 20mA and 20V supply)
  • Safety Description: 28V 300Ohms 93mA

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7707+ SWITCH INPUTS AND SWITCHED OUTPUTS
ZENNER BARRIER
Zones: 2
Ex II 3 G
Ex nA IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number of channels: 2
  • Supply Voltage: 10 to 35V dc (w.r.t earth)
  • Output Current: Up to 35mA
  • Supply Current: Load out + 1.6mA, supply <26V
  • Supply Current: Limited to 50mA, supply >28 or low load resistance
  • Safety Description: 28V 300Ohms 93mA

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7728+ CONTROLLER OUTPUTS, SOLENOIDS
ZENNER BARRIER
Zones: 2
Ex II 3 G
Ex nA IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number of channels: One
  • Supply Voltage: 22.9 to 30V dc w.r.t earth
  • Input Characteristics: Relay energised if input >2.1mA (<2k Ohms)
  • Input Characteristics: Relay de-energised if input <1.2mA (>10k Ohms)
  • Relay Contacts: 50V ac 0.5A. Resistive
  • Relay Contacts: 30V dc 1A. Resistive
  • Supply Current: 26mA maximum @ 24V
  • Response Time: <10ms

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 774X PROXIMITY SWITCH, SOLID STATE OUTPUT AND LINE FAULT DETECT
ZENNER BARRIER
Zones: 2
Ex II 3 G
Ex nA nC IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number Of Channels: One
  • Supply Voltage: 20 to 35V dc w.r.t earth
  • Supply Current: 20mA Maximum @ 24V
  • Input Characteristics: Output energised if input >2.1mA (<2k Ohms)
  • Input Characteristics: Output de-energised if input <1.2mA (>10 Ohms)
  • Operating frequency: dc to 2.5kHz
  • Max Off-state Voltage: 35V
  • Max Off-state leakage: 10?A
  • Max On-state Current: 50mA
  • Max On-state Voltage Drop:
  • <1.41V @ 50mA
  • <1.22V @ 2mA
  • Typical: <1V

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7755AC 2- OR 3- WIRE RTDS (FLOATING BRIDGE)
ZENNER BARRIER
Zones: 2
Ex II 3 G
Ex nA IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number of channels: Two
  • Safety Description: 10V 19mA
  • Supply Voltage 22.9 to 30V dc w.r.t earth
  • Input Characteristics:
  • Relay energised If Input >2.1mA (<2k Ohms)
  • Relay de-energised if input <1.2mA (>10k Ohms)
  • Relay Contacts:
  • 50V ac 0.5A. Resistive
  • 30V dc 1A. Resistive
  • Supply Current: 45mA mAXIMIM @ 24v
  • Response Time: <10ms

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7756AC 3- WIRE RTDS (GROUNDED BRIDGE)
ZENNER BARRIER
Zones: 2
Ex II 3 G
Ex nA IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number Of Channels: Two
  • Safety Description: 10V 19mA
  • Supply Voltage: 20 to 35V dc w.r.t earth
  • Supply Current: 29mA Maximum @ 24V
  • Input Characteristics:
  • Output energised if input >2.1mA (<2k Ohms)
  • Output de-energised if input <1.2mA (>10k Ohms)
  • Output Characteristics:
  • Operating frequency: dc to 2.5kHz
  • Max Off-state Voltage: 35V
  • Max Off-state Leakage: 10?A
  • Max On-state Voltage Drop:
  • 1.41V @ 50mA
  • 1.

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7760AC ACTIVE DC & AC SENSORS THERMOCOUPLES
ZENNER BARRIER
Zones: a
Ex II 3 G
Ex nA IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number of Channels: One
  • Supply Voltage: 22.9 to 30V dc w.r.t earth
  • LFD relay + Red LED: Energised Input <50?A or <100 Ohms
  • Supply Current: 38mA maximum @ 24V
  • Response Time: <10ms
  • Relay Contacts:
  • 50V ac 0.5A. Resisitive
  • 30V dc 1A. Resistive
  • Input Characteristic:
  • Output energised if input >2.1mA (<2k Ohms)
  • Output de-energised if input <1.2mA (>10k Ohms)

Add to enquiry

Thank you, this has been added, click here to view your enquiry.

MTL 7787+/- TRANSMITTERS CONTROLLER OUTPUT, SWITCHES
ZENNER BARRIER
Zones: 2
Ex II 3 G
Ex nA IIC T4 Gc

II [1] GD [EEx ia] IIC
(-20°C to +60°C)

II [1] GD [EEx ia] IIB
(-20°C to +60°C)

ATEX, IECEx
  • Number of Channels: one
  • 2 Wire Transmitter
  • Signal Output: 4/20mA
  • Power Supply: 26V
  • Vwkg: 12.9V
  • Load Resistance: 250Ohms

Add to enquiry